2007 Energy Champions announced ![]()
October 26, 2007
2007 Save Energy Now Recognition Awards announced ![]()
October 26, 2007
| Assessment Date | 06/13/2002 |
| SIC | 2033 |
| SIC Description | Canned Fruits And Vegetables |
| NAICS | |
| NAICS Decription | |
| Principal Product | Juice |
| Sales | $135,000,000 |
| # of Employees | 185 |
| Plant Area (Sq.Ft.) | 0 |
| Annual Production | 0 |
| Production Hrs. Annual | 5,200 |
| Location (State | CA |
| Fiscal Year (Budget Year) | 2002 |
| Yearly Energy Cost | $1,007,827 |
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
Electricity |
6,488,640 KWh | $630,508 | $0.097 |
- Demand Charge |
14,407KW-Month/Year | $175,474 | $12.18 |
- Electricity Fees |
- | $0 | - |
Natural Gas |
39,391 MMBtu | $201,845 | $5.12 |
| Energy Sources | Yearly Usage | Yearly Cost | % Saved | Unit Price |
Electricity |
1,691,192 KWh | $185,088 | 29% | $0.097 |
- Demand Charge |
0 KW-Month/Year | $0 | 0% | $0.097 |
Natural Gas |
13,320 MMBtu | $65,200 | 32% | $5.12 |
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||
| 1 | view details |
REDUCE TEMPERATURE OF PROCESS EQUIPMENT WHEN ON STANDBY | 2.6241 | N | $7,960 | $31,136 | 0.3 | ||||||
|
|||||||||||||
| 2 | view details |
USE MOST EFFICIENT EQUIPMENT AT IT'S MAXIMUM CAPACITY AND LESS EFFICIENT EQUIPMENT ONLY WHEN NECESSARY | 2.6221 | I | $50,000 | $107,810 | 0.5 | ||||||
|
|||||||||||||
| 3 | view details |
RECOVER HEAT FROM AIR COMPRESSOR | 2.2434 | N | $19,350 | $36,936 | 0.5 | ||||||
|
|||||||||||||
| 4 | view details |
REDUCE FLUID FLOW RATES | 2.5123 | I | $16,627 | $31,494 | 0.5 | ||||||
|
|||||||||||||
| 5 | view details |
INSTALL OCCUPANCY SENSORS | 2.7135 | N | $1,200 | $2,185 | 0.5 | ||||||
|
|||||||||||||
| 6 | view details |
USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS | 2.4133 | I | $4,110 | $6,304 | 0.7 | ||||||
|
|||||||||||||
| 7 | view details |
ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO | 2.1233 | I | $17,580 | $21,274 | 0.8 | ||||||
|
|||||||||||||
| 8 | view details |
REDUCE EXCESSIVE BOILER BLOWDOWN | 2.1241 | I | $6,000 | $6,671 | 0.9 | ||||||
|
|||||||||||||
| 9 | view details |
INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS | 2.7132 | N | $2,500 | $2,672 | 0.9 | ||||||
|
|||||||||||||
| 10 | view details |
USE INSULATION IN FURNACES TO FACILITATE HEATING / COOLING | 2.1121 | N | $393 | $319 | 1.2 | ||||||
|
|||||||||||||
| 11 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $14,055 | $3,487 | 4.0 | ||||||
|
|||||||||||||
| 12 | view details |
TREAT AND REUSE RINSE WATERS | 3.4113 | P | $18,705 | $218,183 | 0.1 | ||||||
|
|||||||||||||
| 13 | view details |
RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS | 2.3132 | N | $0 | $8,739 | 0.0 | ||||||
|
|||||||||||||
| 14 | view details |
OPTIMIZE PLANT POWER FACTOR | 2.3212 | N | $3,651 | $2,389 | 1.5 | ||||||
|
|||||||||||||
| 15 | view details |
CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE | 2.8114 | N | $160,000 | $72,375 | 2.2 | ||||||
|
|||||||||||||
| 16 | view details |
INSTALL AUTOMATIC PACKING EQUIPMENT | 4.4410 | I | $350,000 | $101,519 | 3.4 | ||||||
|
|||||||||||||
Rutgers CAES | Industrial Technologies Program Home |
EERE Home
U.S. Department of Energy
| Webmaster |
USA.gov
Content Last Updated: 11/13/2007