Energy Efficiency and Renewable Energy
EERE Home
About the ProgramProgram AreasInformation ResourcesFinancial OpportunitiesTechnologiesDeploymentHome
DOE IAC Database
Industry Classification:
SIC
Search By:
IAC Field Managers

Site Map
EERE Information Center

News

2007 Energy Champions announced 

October 26, 2007

2007 Save Energy Now Recognition Awards announced 

October 26, 2007

Features
Top Ten List of Recommendations
Download IAC Database

Valid HTML 4.01 Strict Valid CSS!

Printable Version

Industrial Assessment Centers

Assessment #OK0783


Assessment Date08/04/2009
SIC2068
SIC DescriptionSalted And Roasted Nuts And Seeds
NAICS311911
NAICS DecriptionRoasted Nuts and Peanut Butter Manufacturing
Principal ProductPeanut Products
Sales$250,000,000
# of Employees300
Plant Area (Sq.Ft.)318,000
Annual Production145,000,000 Pounds
Production Hrs. Annual8,760
Location (StateAR
Fiscal Year (Budget Year)2009
Yearly Energy Cost$2,130,931

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

22,394,101 KWh $1,170,350 $0.052

- Demand Charge

0KW-Month/Year $0

- Electricity Fees

- $0 -

Natural Gas

101,546 MMBtu $960,581 $9.46

Recommended Reduction in Usage & Costs

Energy Sources Yearly Usage Yearly Cost % Saved Unit Price

Electricity

960,517 KWh $48,528 4% $0.052

Natural Gas

12,136 MMBtu $128,271 13% $9.46

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
1 view
details
REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL 2.7232 $280,000 $29,321 9.5
Energy Type Usage Savings Cost Savings
Electrical Consumption 560,640 $29,321
2 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 $887 $112 7.9
Energy Type Usage Savings Cost Savings
Electrical Consumption 2,132 $112
3 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 $775 $1,151 0.7
Energy Type Usage Savings Cost Savings
Electrical Consumption 21,999 $1,151
4 view
details
INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT 2.7241 $26,066 $8,327 3.1
Energy Type Usage Savings Cost Savings
Electrical Consumption 157,500 $8,327
5 view
details
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS 2.4141 $15,039 $4,219 3.6
Energy Type Usage Savings Cost Savings
Electrical Consumption 104,947 $4,219
6 view
details
USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT COMBUSTION AIR 2.2411 $67,320 $58,392 1.2
Energy Type Usage Savings Cost Savings
Natural Gas 5,519 $58,392
7 view
details
ADJUST BURNERS FOR EFFICIENT OPERATION 2.1133 $3,810 $18,978 0.2
Energy Type Usage Savings Cost Savings
Natural Gas 1,797 $18,978
8 view
details
USE HEAT IN FLUE GASES TO PREHEAT PRODUCTS OR MATERIALS 2.2424 $15,708 $50,901 0.3
Energy Type Usage Savings Cost Savings
Natural Gas 4,820 $50,901
9 view
details
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED 2.4231 $0 $5,398 0.0
Energy Type Usage Savings Cost Savings
Electrical Consumption 113,299 $5,398




Rutgers CAES | Industrial Technologies Program Home | EERE Home
U.S. Department of Energy | Webmaster | USA.gov