Assessment #MI0186


Assessment Date08/25/2009
SIC3845
SIC DescriptionElectromedical Equipment
NAICS334510
NAICS DecriptionElectromedical and Electrotherapeutic Apparatus Manufacturing
Principal ProductBlood testing equipment
Sales$50,000,000
# of Employees475
Plant Area (Sq.Ft.)500,000
Annual Production125,000
Production Hrs. Annual6,732
Location (StateFL
Fiscal Year (Budget Year)2009
Yearly Energy Cost$2,041,948

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

16,453,831 KWh $1,424,057 $0.087

- Demand Charge

59,073KW-Month/Year $328,603 $5.56

- Electricity Fees

- $289,288 -

Recommended Reduction in Usage & Costs

Energy Sources Yearly Usage Yearly Cost % Saved Unit Price

Electricity

4,784,677 KWh $385,216 27% $0.087

- Demand Charge

8,529 KW-Month/Year $46,288 14% $0.087

- Electricity Fees

0 KWh $0 0% $0.087

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
1 view
details
UTILIZE A LESS EXPENSIVE COOLING METHOD 2.2628 $460,000 $160,282 2.9
Energy Type Usage Savings Cost Savings
Electrical Consumption 1,782,634 $142,612
Electrical Demand 3,178 $17,670
2 view
details
LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA 2.7221 $2,000 $110,625 0.0
Energy Type Usage Savings Cost Savings
Electrical Consumption 1,230,403 $98,432
Electrical Demand 2,193 $12,193
3 view
details
UTILIZE A LESS EXPENSIVE COOLING METHOD 2.2628 $105,070 $76,266 1.4
Energy Type Usage Savings Cost Savings
Electrical Consumption 848,232 $67,859
Electrical Demand 1,512 $8,407
4 view
details
TURN OFF EQUIPMENT WHEN NOT IN USE 2.6218 $25,000 $56,948 0.4
Energy Type Usage Savings Cost Savings
Electrical Consumption 618,836 $51,948
Electrical Demand 1,103 $5,000
5 view
details
CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD 2.7425 $73,500 $24,293 3.0
Energy Type Usage Savings Cost Savings
Electrical Consumption 270,192 $21,615
Electrical Demand 482 $2,678
6 view
details
DISCONNECT BALLASTS 2.7122 $1,450 $3,090 0.5
Energy Type Usage Savings Cost Savings
Electrical Consumption 34,380 $2,750
Electrical Demand 61 $340




Rutgers CAES | Industrial Technologies Program Home | EERE Home
U.S. Department of Energy | Webmaster | USA.gov

Content Last Updated: 11/13/2007