Industrial Assessment Centers
Assessment #WV0407
| Assessment Year | 2010 |
|---|---|
| SIC | 2869 |
| SIC Description | Industrial Organic Chemicals, Nec |
| NAICS | 325199 |
| NAICS Description | All Other Basic Organic Chemical Manufacturing |
| Principal Product | organo functional silanes |
| Sales | $ 10,000,000 |
| # of Employees | 210 |
| Plant Area (Sq.Ft.) | 457,000 |
| Annual Production | 38,000,000 Pounds |
| Production Hrs. Annual | 8,760 |
| Location (State) | WV |
| Yearly Energy Cost | $ 6,710,622 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
55,103,450 kWh | $ 1,655,601 | $ 0.030 /kWh |
- Demand Charge |
88,405 kW | $ 877,398 | $ 9.92 /kW |
- Electricity Fees |
- | $ 0 | - |
Natural Gas |
560,430 MMBtu | $ 4,177,623 | $ 7.45 /MMBtu |
TOTAL ENERGY |
1,125,240 MMBtu | $ 6,710,622 | $ 5.96 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
42,823,956 kWh 647,994 kWh |
$ 1,285,678 $ 19,473 |
77.66 % 1.18 % |
$ 0.030 /kWh |
- Demand Charge |
58,788 kW 912 kW |
$ 583,184 $ 9,054 |
66.47 % 1.03 % |
$ 9.92 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
-42,113 MMBtu 34,721 MMBtu |
$ -313,743 $ 258,671 |
-7.51 % 6.19 % |
$ 7.45 /MMBtu |
TOTAL ENERGY |
396,832 MMBtu 41,363 MMBtu |
$ 1,555,119 $ 287,198 |
23.17 % 4.28 % |
$ 5.96 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
INSTALL WASTE HEAT BOILER TO PRODUCE STEAM | 2.2423 | N | $ 798,300 | $ 622,016 | 1.28 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 02 | view details |
USE STEAM PRESSURE REDUCTION TO GENERATE POWER | 2.3321 | N | $ 1,200,000 | $ 542,540 | 2.21 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 03 | view details |
REPAIR OR REPLACE STEAM TRAPS | 2.2113 | I | $ 5,500 | $ 235,631 | 0.02 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 04 | view details |
USE RADIANT HEATER FOR SPOT HEATING | 2.7231 | N | $ 96,200 | $ 43,962 | 2.19 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 05 | view details |
DIRECT WARMEST AIR TO COMBUSTION INTAKE | 2.1213 | N | $ 7,920 | $ 20,301 | 0.39 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 06 | view details |
RECOVER WASTE HEAT FROM EQUIPMENT | 2.2437 | N | $ 43,400 | $ 19,102 | 2.27 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 07 | view details |
DEVELOP A REPAIR/REPLACE POLICY | 2.4151 | I | $ 772 | $ 10,842 | 0.07 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 08 | view details |
USE MORE EFFICIENT LIGHT SOURCE | 2.7143 | I | $ 17,348 | $ 5,003 | 3.47 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 09 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | I | $ 7,158 | $ 3,209 | 2.23 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 10 | view details |
ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM | 2.4157 | I | $ 1,000 | $ 4,353 | 0.23 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||