Industrial Assessment Centers
Assessment #UF0429
| Assessment Year | 2009 |
|---|---|
| SIC | 2086 |
| SIC Description | Bottled And Canned Soft Drinks |
| NAICS | 312111 |
| NAICS Description | Soft Drink Manufacturing |
| Principal Product | purified water and carbonated soft drinks |
| Sales | $ 87,900,000 |
| # of Employees | 110 |
| Plant Area (Sq.Ft.) | 17,500 |
| Annual Production | 23,000,000 Not Available |
| Production Hrs. Annual | 2,080 |
| Location (State) | FL |
| Yearly Energy Cost | $ 1,417,698 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
9,786,420 kWh | $ 838,834 | $ 0.086 /kWh |
- Demand Charge |
21,088 kW | $ 191,416 | $ 9.08 /kW |
- Electricity Fees |
- | $ 122,049 | - |
Natural Gas |
65,979 MMBtu | $ 265,399 | $ 4.02 /MMBtu |
TOTAL ENERGY |
166,291 MMBtu | $ 1,417,698 | $ 8.53 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
2,042,946 kWh 620,350 kWh |
$ 204,855 $ 63,434 |
24.42 % 7.56 % |
$ 0.086 /kWh |
- Demand Charge |
53 kW 26 kW |
$ 484 $ 236 |
0.25 % 0.12 % |
$ 9.08 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
11,403 MMBtu 83 MMBtu |
$ 45,848 $ 334 |
17.28 % 0.13 % |
$ 4.02 /MMBtu |
TOTAL ENERGY |
32,342 MMBtu 6,441 MMBtu |
$ 251,187 $ 64,004 |
17.72 % 4.51 % |
$ 8.53 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED | 2.7124 | I | $ 0 | $ 1,635 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 02 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | I | $ 0 | $ 19,766 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 03 | view details |
REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS | 2.7111 | N | $ 0 | $ 4,130 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 04 | view details |
LOWER LIGHT FIXTURES IN HIGH CEILING AREAS | 2.7141 | N | $ 0 | $ 1,899 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 05 | view details |
REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC | 2.1131 | I | $ 0 | $ 334 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 06 | view details |
USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS | 2.4133 | N | $ 0 | $ 12,625 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 07 | view details |
PREHEAT COMBUSTION AIR WITH WASTE HEAT | 2.2442 | N | $ 0 | $ 45,514 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 08 | view details |
REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC | 2.1131 | N | $ 0 | $ 2,119 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 09 | view details |
INSTALL ADEQUATE DRYERS ON AIR LINES TO ELIMINATE BLOWDOWN | 2.4222 | N | $ 0 | $ 19,795 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 10 | view details |
USE ADJUSTABLE FREQUENCY DRIVE TO REPLACE MOTOR-GENERATOR SET | 2.4142 | N | $ 0 | $ 2,346 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 11 | view details |
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS | 2.4221 | N | $ 0 | $ 14,435 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 12 | view details |
UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED | 2.6231 | N | $ 0 | $ 16,025 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 13 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | I | $ 0 | $ 42,269 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 14 | view details |
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED | 2.4231 | N | $ 0 | $ 68,295 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||