Industrial Assessment Centers

Assessment #SU0310


Assessment Year 2011
SIC 2451
SIC Description Mobile Homes
NAICS 321991
NAICS Description Manufactured Home (Mobile Home) Manufacturing
Principal Product Manufactured Housing
Sales $ 18,100,000
# of Employees 95
Plant Area (Sq.Ft.) 182,000
Annual Production 733 Pieces
Production Hrs. Annual 2,210
Location (State) NY
Yearly Energy Cost $ 127,276

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

845,324 kWh $ 53,550 $ 0.063 /kWh

- Demand Charge

4,650 kW $ 18,472 $ 3.97 /kW

- Electricity Fees

- $ 13,868 -

Natural Gas

4,327 MMBtu $ 41,386 $ 9.56 /MMBtu

TOTAL ENERGY

12,992 MMBtu $ 127,276 $ 9.80 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

194,636 kWh
54,266 kWh
$ 12,283
$ 3,425
22.94 %
6.40 %
$ 0.063 /kWh

- Demand Charge

790 kW
0 kW
$ 3,136
$ 0
16.98 %
0.00 %
$ 3.97 /kW

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

961 MMBtu
0 MMBtu
$ 9,575
$ 0
23.14 %
0.00 %
$ 9.56 /MMBtu

TOTAL ENERGY

2,956 MMBtu
556 MMBtu
$ 24,994
$ 3,425
19.64 %
2.69 %
$ 9.80 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES 2.8121 I $ 0 $ 5,591 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

One-time Revenue or Avoided Cost

- $ 5,591 -

TOTAL PRODUCTON

- $ 5,591 -
02 view
details
CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE 2.8114 I $ 0 $ 2,577 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

One-time Revenue or Avoided Cost

- $ 2,577 -

TOTAL PRODUCTON

- $ 2,577 -
03 view
details
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED 2.4231 I $ 0 $ 809 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

12,818 kWh $ 809 $ 0.063 /kWh

TOTAL ENERGY

131 MMBtu $ 809 -
04 view
details
USE MORE EFFICIENT LIGHT SOURCE 2.7143 N $ 287 $ 704 0.41
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

4,231 kWh $ 267 $ 0.063 /kWh

- Demand Charge

6 kW $ 23 $ 3.97 /kW

TOTAL ENERGY

43 MMBtu $ 290 -

Personnel Changes

- $ 260 -

One-time Revenue or Avoided Cost

- $ 154 -

TOTAL PRODUCTON

- $ 414 -
05 view
details
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES 2.4236 I $ 1,200 $ 2,357 0.51
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

37,349 kWh $ 2,357 $ 0.063 /kWh

TOTAL ENERGY

383 MMBtu $ 2,357 -
06 view
details
IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS 2.7243 N $ 11,900 $ 8,216 1.45
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

-19,843 kWh $ -1,252 $ 0.063 /kWh

- Demand Charge

-27 kW $ -107 $ 3.97 /kW

Natural Gas

961 MMBtu $ 9,575 $ 9.56 /MMBtu

TOTAL ENERGY

757 MMBtu $ 8,216 -
07 view
details
CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES 2.6211 I $ 467 $ 259 1.80
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

4,099 kWh $ 259 $ 0.063 /kWh

TOTAL ENERGY

42 MMBtu $ 259 -
08 view
details
INSTALL OCCUPANCY SENSORS 2.7135 N $ 778 $ 416 1.87
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

6,586 kWh $ 416 $ 0.063 /kWh

TOTAL ENERGY

68 MMBtu $ 416 -
09 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 N $ 44,892 $ 12,647 3.55
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

149,396 kWh $ 9,427 $ 0.063 /kWh

- Demand Charge

811 kW $ 3,220 $ 3.97 /kW

TOTAL ENERGY

1,531 MMBtu $ 12,647 -