Industrial Assessment Centers
Assessment #SF0410
| Assessment Year | 2012 |
|---|---|
| SIC | 4952 |
| SIC Description | Sewerage Systems |
| NAICS | 221320 |
| NAICS Description | Sewage Treatment Facilities |
| Principal Product | Recycled Water |
| Sales | $ 500,000 |
| # of Employees | 73 |
| Plant Area (Sq.Ft.) | 1,600,000 |
| Annual Production | 4,745,000 Thousand Gallons |
| Production Hrs. Annual | 8,760 |
| Location (State) | HI |
| Yearly Energy Cost | $ 2,966,675 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
12,127,200 kWh | $ 2,603,536 | $ 0.215 /kWh |
- Demand Charge |
20,174 kW | $ 363,139 | $ 18.00 /kW |
- Electricity Fees |
- | $ 0 | - |
TOTAL ENERGY |
124,305 MMBtu | $ 2,966,675 | $ 23.87 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
2,777,574 kWh 2,777,574 kWh |
$ 596,296 $ 596,296 |
22.90 % 22.90 % |
$ 0.215 /kWh |
- Demand Charge |
4,110 kW 4,110 kW |
$ 73,946 $ 73,946 |
20.36 % 20.36 % |
$ 18.00 /kW |
- Electricity Fees |
- |
$ 5,647 $ 5,647 |
0.00 % 0.00 % |
- |
TOTAL ENERGY |
28,470 MMBtu 28,470 MMBtu |
$ 675,889 $ 675,889 |
22.78 % 22.78 % |
$ 23.87 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS | 2.7224 | I | $ 0 | $ 33,835 | 0.00 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 02 | view details |
UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS | 2.4111 | I | $ 129 | $ 1,290 | 0.10 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 03 | view details |
USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS | 2.4133 | I | $ 1,452 | $ 11,966 | 0.12 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 04 | view details |
REDUCE FLUID FLOW RATES | 2.5123 | I | $ 4,715 | $ 20,646 | 0.23 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 05 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | I | $ 70,219 | $ 156,563 | 0.45 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 06 | view details |
REDUCE FLUID FLOW RATES | 2.5123 | I | $ 33,080 | $ 41,557 | 0.80 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 07 | view details |
REPLACE OVER-SIZE MOTORS AND PUMPS WITH OPTIMUM SIZE | 2.4131 | I | $ 165,923 | $ 121,698 | 1.36 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 08 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | I | $ 156,543 | $ 86,008 | 1.82 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 09 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | I | $ 353,108 | $ 178,304 | 1.98 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||
| 10 | view details |
INSTALL OCCUPANCY SENSORS | 2.7135 | I | $ 71,940 | $ 24,022 | 2.99 | ||||||||||||||||||||
|
|||||||||||||||||||||||||||