Industrial Assessment Centers

Assessment #SF0270


Assessment Year 2003
SIC 2084
SIC Description Wines, Brandy, And Brandy Spirits
NAICS 312130
NAICS Description Wineries
Principal Product Wines
Sales $ 72,000,000
# of Employees 53
Plant Area (Sq.Ft.) 100,000
Annual Production 0 Not Available
Production Hrs. Annual 5,137
Location (State) CA
Yearly Energy Cost $ 190,101

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

1,338,640 kWh $ 140,507 $ 0.105 /kWh

- Demand Charge

3,811 kW $ 39,460 $ 10.35 /kW

- Electricity Fees

- $ 0 -

Natural Gas

1,676 MMBtu $ 10,134 $ 6.05 /MMBtu

TOTAL ENERGY

15,397 MMBtu $ 190,101 $ 12.35 /MMBtu

Solid Waste (non-haz)

197 lbs $ 22,176 $ 0 /lbs

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

253,037 kWh
127,322 kWh
$ 26,563
$ 13,364
18.91 %
9.51 %
$ 0.105 /kWh

- Demand Charge

469 kW
449 kW
$ 5,039
$ 4,837
12.77 %
12.26 %
$ 10.35 /kW

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

0 MMBtu
0 MMBtu
$ 0
$ 0
0.00 %
0.00 %
$ 6.05 /MMBtu

TOTAL ENERGY

2,594 MMBtu
1,305 MMBtu
$ 31,602
$ 18,201
16.62 %
9.57 %
$ 12.35 /MMBtu

Solid Waste (non-haz)

408 lbs
0 lbs
$ 9,418
$ 0
42.47 %
0.00 %
$ 0 /lbs

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT 2.7241 N $ 0 $ 2,671 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

25,446 kWh $ 2,671 $ 0.105 /kWh

TOTAL ENERGY

261 MMBtu $ 2,671 -
02 view
details
TURN OFF EQUIPMENT WHEN NOT IN USE 2.6218 N $ 0 $ 244 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

2,329 kWh $ 244 $ 0.105 /kWh

TOTAL ENERGY

24 MMBtu $ 244 -
03 view
details
KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE 2.7442 N $ 4,145 $ 9,405 0.44
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

89,566 kWh $ 9,405 $ 0.105 /kWh

TOTAL ENERGY

918 MMBtu $ 9,405 -
04 view
details
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS 2.4141 I $ 9,485 $ 14,226 0.67
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

102,332 kWh $ 10,741 $ 0.105 /kWh

- Demand Charge

318 kW $ 3,485 $ 10.35 /kW

TOTAL ENERGY

1,049 MMBtu $ 14,226 -
05 view
details
UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS 2.4111 N $ 830 $ 1,081 0.77
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

8,374 kWh $ 879 $ 0.105 /kWh

- Demand Charge

20 kW $ 202 $ 10.35 /kW

TOTAL ENERGY

86 MMBtu $ 1,081 -
06 view
details
INSTALL SKYLIGHTS 2.7145 I $ 10,800 $ 3,975 2.72
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

24,990 kWh $ 2,623 $ 0.105 /kWh

- Demand Charge

131 kW $ 1,352 $ 10.35 /kW

TOTAL ENERGY

256 MMBtu $ 3,975 -
07 view
details
IMPLEMENT A REGULAR MAINTENANCE PROGRAM TO REDUCE EMISSIONS FROM LEAKY VALVES AND PIPE FITTINGS 3.7312 N $ 0 $ 3,034 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Ancillary Material Cost

- $ 3,034 -

TOTAL PRODUCTON

- $ 3,034 -
08 view
details
INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS 3.6193 N $ 9,500 $ 9,418 1.01
Energy Sources Yearly Reduction Yearly Savings Unit Price

Solid Waste (non-haz)

408 lbs $ 9,418 $ 0 /lbs

TOTAL WASTE

- $ 9,418 -
09 view
details
ADOPT IN-HOUSE MATERIAL GENERATION 4.2120 N $ 80,393 $ 15,179 5.30
Energy Sources Yearly Reduction Yearly Savings Unit Price

Ancillary Material Cost

- $ 15,179 -

TOTAL PRODUCTON

- $ 15,179 -