Industrial Assessment Centers

Assessment #SD0452


Assessment Year 2012
SIC 4952
SIC Description Sewerage Systems
NAICS 221310
NAICS Description Water Supply and Irrigation Systems
Principal Product Treated Water
Sales $ 10,000,000
# of Employees 13
Plant Area (Sq.Ft.) 2,560,000
Annual Production 11,500 Thousand Gallons
Production Hrs. Annual 8,760
Location (State) CA
Yearly Energy Cost $ 1,703,133

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

11,979,368 kWh $ 1,045,469 $ 0.087 /kWh

- Demand Charge

25,575 kW $ 388,588 $ 15.19 /kW

- Electricity Fees

- $ 11,590 -

Natural Gas

46,277 MMBtu $ 257,486 $ 5.56 /MMBtu

TOTAL ENERGY

169,067 MMBtu $ 1,703,133 $ 10.07 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

1,062,689 kWh
969,585 kWh
$ 92,773
$ 84,645
8.87 %
8.10 %
$ 0.087 /kWh

- Demand Charge

1,509 kW
1,381 kW
$ 22,922
$ 20,977
5.90 %
5.40 %
$ 15.19 /kW

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

14,338 MMBtu
14,338 MMBtu
$ 79,775
$ 79,775
30.98 %
30.98 %
$ 5.56 /MMBtu

TOTAL ENERGY

25,230 MMBtu
24,276 MMBtu
$ 195,469
$ 185,397
11.48 %
10.89 %
$ 10.07 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
INSTALL EQUIPMENT TO UTILIZE WASTE FUEL 2.1336 I $ 2,000 $ 48,619 0.04
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

8,738 MMBtu $ 48,619 $ 5.56 /MMBtu

TOTAL ENERGY

8,738 MMBtu $ 48,619 -
02 view
details
USE / PURCHASE OPTIMUM SIZED COMPRESSOR 2.4226 I $ 15,925 $ 24,957 0.64
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

219,585 kWh $ 19,170 $ 0.087 /kWh

- Demand Charge

381 kW $ 5,787 $ 15.19 /kW

TOTAL ENERGY

2,251 MMBtu $ 24,957 -
03 view
details
CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS 3.1191 N $ 18,680 $ 10,072 1.85
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

93,104 kWh $ 8,128 $ 0.087 /kWh

- Demand Charge

128 kW $ 1,944 $ 15.19 /kW

TOTAL ENERGY

954 MMBtu $ 10,072 -
04 view
details
USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT COMBUSTION AIR 2.2411 I $ 4,200 $ 2,223 1.89
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

400 MMBtu $ 2,223 $ 5.56 /MMBtu

TOTAL ENERGY

400 MMBtu $ 2,223 -
05 view
details
USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT 2.3415 I $ 275,000 $ 102,098 2.69
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

750,000 kWh $ 65,475 $ 0.087 /kWh

- Demand Charge

1,000 kW $ 15,190 $ 15.19 /kW

Natural Gas

5,200 MMBtu $ 28,933 $ 5.56 /MMBtu

TOTAL ENERGY

12,888 MMBtu $ 109,598 -

Administrative Changes

- $ -7,500 -

TOTAL PRODUCTON

- $ -7,500 -