Industrial Assessment Centers

Assessment #RU0089


Assessment Year 1990
SIC 3061
SIC Description Mechanical Rubber Goods
NAICS
NAICS Description
Principal Product MOLDED RUBBER PRODUCTS
Sales $ 3,500,000
# of Employees 80
Plant Area (Sq.Ft.) 0
Annual Production 16 Tons
Production Hrs. Annual 4,000
Location (State) NY
Yearly Energy Cost $ 150,062

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

1,038,980 kWh $ 106,376 $ 0.102 /kWh

- Electricity Fees

- $ 0 -

Natural Gas

8,390 MMBtu $ 43,686 $ 5.21 /MMBtu

TOTAL ENERGY

19,040 MMBtu $ 150,062 $ 7.88 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

11,430 kWh
2,344 kWh
$ 1,168
$ 237
1.10 %
0.22 %
$ 0.102 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

806 MMBtu
741 MMBtu
$ 21,099
$ 20,760
48.30 %
47.52 %
$ 5.21 /MMBtu

TOTAL ENERGY

923 MMBtu
765 MMBtu
$ 22,267
$ 20,997
14.84 %
13.99 %
$ 7.88 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO 2.1233 I $ 500 $ 2,307 0.22
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

420 MMBtu $ 2,307 $ 5.21 /MMBtu

TOTAL ENERGY

420 MMBtu $ 2,307 -
02 view
details
INSTALL / REPAIR INSULATION ON CONDENSATE LINES 2.2122 N $ 75 $ 339 0.22
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

65 MMBtu $ 339 $ 5.21 /MMBtu

TOTAL ENERGY

65 MMBtu $ 339 -
03 view
details
CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE 2.8114 I $ 5,000 $ 16,780 0.30
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

0 MMBtu $ 16,780 $ 5.21 /MMBtu

TOTAL ENERGY

0 MMBtu $ 16,780 -
04 view
details
IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS 2.7243 I $ 2,520 $ 1,389 1.81
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

-2,638 kWh $ -284 $ 0.102 /kWh

Natural Gas

321 MMBtu $ 1,673 $ 5.21 /MMBtu

TOTAL ENERGY

294 MMBtu $ 1,389 -
05 view
details
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS 2.4221 N $ 68 $ 931 0.07
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

9,086 kWh $ 931 $ 0.102 /kWh

TOTAL ENERGY

93 MMBtu $ 931 -
06 view
details
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES 2.4236 I $ 300 $ 521 0.58
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

4,982 kWh $ 521 $ 0.102 /kWh

TOTAL ENERGY

51 MMBtu $ 521 -