Industrial Assessment Centers

Assessment #RU0060


Assessment Year 1989
SIC 3272
SIC Description Concrete Products, Nec
NAICS
NAICS Description
Principal Product PRESTRESSED CONCRETE
Sales $ 25,000,000
# of Employees 175
Plant Area (Sq.Ft.) 0
Annual Production 200 Thousand Feet
Production Hrs. Annual 5,049
Location (State) MD
Yearly Energy Cost $ 521,984

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

4,149,473 kWh $ 269,636 $ 0.065 /kWh

- Electricity Fees

- $ 0 -

Fuel Oil #4

83,805 MMBtu $ 252,348 $ 3.01 /MMBtu

TOTAL ENERGY

126,337 MMBtu $ 521,984 $ 4.13 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

252,931 kWh
252,931 kWh
$ 16,436
$ 16,436
6.10 %
6.10 %
$ 0.065 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Fuel Oil #4

17,631 MMBtu
15,686 MMBtu
$ 53,073
$ 47,217
21.03 %
18.71 %
$ 3.01 /MMBtu

TOTAL ENERGY

20,223 MMBtu
18,278 MMBtu
$ 69,509
$ 63,653
13.32 %
12.19 %
$ 4.13 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
REPAIR LEAKS IN LINES AND VALVES 2.2133 I $ 0 $ 20,786 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Fuel Oil #4

6,905 MMBtu $ 20,786 $ 3.01 /MMBtu

TOTAL ENERGY

6,905 MMBtu $ 20,786 -
02 view
details
REDESIGN FLOW TO MINIMIZE MASS TRANSFER LENGTH 2.5121 I $ 16,835 $ 18,359 0.92
Energy Sources Yearly Reduction Yearly Savings Unit Price

Fuel Oil #4

6,099 MMBtu $ 18,359 $ 3.01 /MMBtu

TOTAL ENERGY

6,099 MMBtu $ 18,359 -
03 view
details
USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES 2.4322 N $ 6,900 $ 5,856 1.18
Energy Sources Yearly Reduction Yearly Savings Unit Price

Fuel Oil #4

1,945 MMBtu $ 5,856 $ 3.01 /MMBtu

TOTAL ENERGY

1,945 MMBtu $ 5,856 -
04 view
details
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES 2.4236 I $ 0 $ 11,256 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

173,212 kWh $ 11,256 $ 0.065 /kWh

TOTAL ENERGY

1,775 MMBtu $ 11,256 -
05 view
details
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS 2.4221 I $ 102 $ 5,180 0.02
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

79,719 kWh $ 5,180 $ 0.065 /kWh

TOTAL ENERGY

817 MMBtu $ 5,180 -
06 view
details
ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO 2.1233 I $ 1,500 $ 8,072 0.19
Energy Sources Yearly Reduction Yearly Savings Unit Price

Fuel Oil #4

2,682 MMBtu $ 8,072 $ 3.01 /MMBtu

TOTAL ENERGY

2,682 MMBtu $ 8,072 -