Industrial Assessment Centers
Assessment #OR0540
| Assessment Year | 2008 |
|---|---|
| SIC | 2869 |
| SIC Description | Industrial Organic Chemicals, Nec |
| NAICS | 325199 |
| NAICS Description | All Other Basic Organic Chemical Manufacturing |
| Principal Product | Process Chemicals |
| Sales | $ 29,000,000 |
| # of Employees | 32 |
| Plant Area (Sq.Ft.) | 49,000 |
| Annual Production | 40,000,000 Pounds |
| Production Hrs. Annual | 8,760 |
| Location (State) | OR |
| Yearly Energy Cost | $ 96,595 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
1,620,000 kWh | $ 95,900 | $ 0.059 /kWh |
- Demand Charge |
4 kW | $ 22 | $ 5.50 /kW |
- Electricity Fees |
- | $ 627 | - |
Natural Gas |
353 MMBtu | $ 46 | $ 0.13 /MMBtu |
TOTAL ENERGY |
16,958 MMBtu | $ 96,595 | $ 5.70 /MMBtu |
Water Disposal |
465,288 Gal | $ 76 | $ 0 /Gal |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
432,467 kWh 24,960 kWh |
$ 28,684 $ 1,561 |
29.91 % 1.63 % |
$ 0.059 /kWh |
- Demand Charge |
5 kW 5 kW |
$ 178 $ 178 |
809.09 % 809.09 % |
$ 5.50 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
1,489 MMBtu 1,489 MMBtu |
$ 14,149 $ 14,149 |
30,758.70 % 30,758.70 % |
$ 0.13 /MMBtu |
TOTAL ENERGY |
5,921 MMBtu 1,745 MMBtu |
$ 43,011 $ 15,888 |
44.53 % 16.45 % |
$ 5.70 /MMBtu |
Water Disposal |
92,032 Gal 92,032 Gal |
$ 8 $ 8 |
10.53 % 10.53 % |
$ 0 /Gal |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
REPLACE CITY WATER WITH RECYCLED WATER VIA COOLING TOWER | 3.4114 | I | $ 10,000 | $ 29 | 344.83 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 02 | view details |
INCREASE AMOUNT OF CONDENSATE RETURNED | 2.2121 | I | $ 6,100 | $ 14,149 | 0.43 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 03 | view details |
INSTALL OCCUPANCY SENSORS | 2.7135 | I | $ 13,049 | $ 2,932 | 4.45 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 04 | view details |
USE SOLAR HEAT TO MAKE ELECTRICTY | 2.9114 | N | $ 257,380 | $ 23,433 | 10.98 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 05 | view details |
USE / PURCHASE OPTIMUM SIZED COMPRESSOR | 2.4226 | N | $ 12,400 | $ 434 | 28.57 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 06 | view details |
ELIMINATE PERMANENTLY THE USE OF COMPRESSED AIR | 2.4233 | N | $ 0 | $ 2,216 | 0.00 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 07 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | N | $ 1,398 | $ 699 | 2.00 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 08 | view details |
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED | 2.4231 | N | $ 0 | $ 341 | 0.00 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||