Industrial Assessment Centers
Assessment #OK0794
| Assessment Year | 2010 |
|---|---|
| SIC | 3593 |
| SIC Description | Fluid Power Cylinders & Actuators |
| NAICS | 333995 |
| NAICS Description | Fluid Power Cylinder and Actuator Manufacturing |
| Principal Product | Hydraulic Cylinder |
| Sales | $ 9,600,000 |
| # of Employees | 87 |
| Plant Area (Sq.Ft.) | 132,500 |
| Annual Production | 92,000 Pieces |
| Production Hrs. Annual | 4,355 |
| Location (State) | KS |
| Yearly Energy Cost | $ 239,524 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
1,917,600 kWh | $ 137,339 | $ 0.072 /kWh |
- Demand Charge |
8,699 kW | $ 40,301 | $ 4.63 /kW |
- Electricity Fees |
- | $ 0 | - |
Natural Gas |
9,482 MMBtu | $ 61,884 | $ 6.53 /MMBtu |
TOTAL ENERGY |
29,138 MMBtu | $ 239,524 | $ 8.22 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
181,136 kWh 19,564 kWh |
$ 12,967 $ 1,400 |
9.44 % 1.02 % |
$ 0.072 /kWh |
- Demand Charge |
0 kW 0 kW |
$ 0 $ 0 |
0.00 % 0.00 % |
$ 4.63 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
3,361 MMBtu 1,317 MMBtu |
$ 25,888 $ 12,132 |
41.83 % 19.60 % |
$ 6.53 /MMBtu |
TOTAL ENERGY |
5,218 MMBtu 1,518 MMBtu |
$ 38,855 $ 13,532 |
16.22 % 5.65 % |
$ 8.22 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA | 2.7221 | I | $ 75,405 | $ 12,132 | 6.22 | ||||||||||||
|
|||||||||||||||||||
| 02 | view details |
INSTALL SET-BACK TIMERS | 2.6232 | N | $ 3,239 | $ 2,786 | 1.16 | ||||||||||||
|
|||||||||||||||||||
| 03 | view details |
USE PROPER THICKNESS OF INSULATION ON BUILDING ENVELOPE | 2.7492 | N | $ 159,840 | $ 10,317 | 15.49 | ||||||||||||
|
|||||||||||||||||||
| 04 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 12,733 | $ 3,034 | 4.20 | ||||||||||||
|
|||||||||||||||||||
| 05 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 68,625 | $ 7,300 | 9.40 | ||||||||||||
|
|||||||||||||||||||
| 06 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 4,978 | $ 853 | 5.84 | ||||||||||||
|
|||||||||||||||||||
| 07 | view details |
RECOVER HEAT FROM AIR COMPRESSOR | 2.2434 | N | $ 3,006 | $ 653 | 4.60 | ||||||||||||
|
|||||||||||||||||||
| 08 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | I | $ 841 | $ 1,400 | 0.60 | ||||||||||||
|
|||||||||||||||||||
| 09 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | N | $ 2,280 | $ 380 | 6.00 | ||||||||||||
|
|||||||||||||||||||