Industrial Assessment Centers

Assessment #OK0401


Assessment Year 1993
SIC 3339
SIC Description Primary Nonferrous Metals, Nec
NAICS
NAICS Description
Principal Product Lenses, Semiconductor Material
Sales $ 11,000,000
# of Employees 107
Plant Area (Sq.Ft.) 36,095
Annual Production 24,000 Pieces
Production Hrs. Annual 8,568
Location (State) OK
Yearly Energy Cost $ 232,616

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

5,402,696 kWh $ 193,453 $ 0.036 /kWh

- Electricity Fees

- $ 0 -

Natural Gas

10,472 MMBtu $ 39,163 $ 3.74 /MMBtu

TOTAL ENERGY

65,850 MMBtu $ 232,616 $ 3.53 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

1,209,554 kWh
253,224 kWh
$ 44,603
$ 10,746
23.06 %
5.55 %
$ 0.036 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

94 MMBtu
94 MMBtu
$ 352
$ 352
0.90 %
0.90 %
$ 3.74 /MMBtu

TOTAL ENERGY

12,493 MMBtu
2,690 MMBtu
$ 44,955
$ 11,098
19.33 %
4.77 %
$ 3.53 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 I $ 648 $ 2,436 0.27
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

67,116 kWh $ 2,436 $ 0.036 /kWh

TOTAL ENERGY

688 MMBtu $ 2,436 -
02 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 I $ 12,281 $ 7,229 1.70
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

143,611 kWh $ 7,229 $ 0.036 /kWh

TOTAL ENERGY

1,472 MMBtu $ 7,229 -
03 view
details
UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED 2.6231 I $ 69 $ 1,081 0.06
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

42,497 kWh $ 1,081 $ 0.036 /kWh

TOTAL ENERGY

436 MMBtu $ 1,081 -
04 view
details
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS 2.4141 N $ 11,720 $ 4,239 2.76
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

140,973 kWh $ 4,239 $ 0.036 /kWh

TOTAL ENERGY

1,445 MMBtu $ 4,239 -
05 view
details
INSTALL / REPAIR INSULATION ON CONDENSATE LINES 2.2122 I $ 168 $ 352 0.48
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

94 MMBtu $ 352 $ 3.74 /MMBtu

TOTAL ENERGY

94 MMBtu $ 352 -
06 view
details
USE INSULATION IN FURNACES TO FACILITATE HEATING / COOLING 2.1121 N $ 8,169 $ 21,033 0.39
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

824,736 kWh $ 21,033 $ 0.036 /kWh

TOTAL ENERGY

8,454 MMBtu $ 21,033 -
07 view
details
USE OUTSIDE COLD WATER SOURCE AS A SUPPLY OF COOLING WATER 2.2692 N $ 31,250 $ 8,585 3.64
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

-9,379 kWh $ 8,585 $ 0.036 /kWh

TOTAL ENERGY

-96 MMBtu $ 8,585 -