Industrial Assessment Centers
Assessment #NC0049
| Assessment Year | 1995 |
|---|---|
| SIC | 3621 |
| SIC Description | Motors And Generators |
| NAICS | |
| NAICS Description | |
| Principal Product | Electronic Components |
| Sales | $ 35,000,000 |
| # of Employees | 190 |
| Plant Area (Sq.Ft.) | 106,000 |
| Annual Production | 5,000 Pieces |
| Production Hrs. Annual | 3,000 |
| Location (State) | NC |
| Yearly Energy Cost | $ 186,219 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
3,143,904 kWh | $ 186,219 | $ 0.059 /kWh |
- Electricity Fees |
- | $ 0 | - |
TOTAL ENERGY |
32,225 MMBtu | $ 186,219 | $ 5.78 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
915,006 kWh 223,916 kWh |
$ 54,142 $ 13,382 |
29.07 % 7.19 % |
$ 0.059 /kWh |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
TOTAL ENERGY |
8,163 MMBtu 2,295 MMBtu |
$ 48,071 $ 13,382 |
25.81 % 7.19 % |
$ 5.78 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | I | $ 1,290 | $ 3,182 | 0.41 | ||||||||||||||||
|
|||||||||||||||||||||||
| 02 | view details |
USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT | 2.7233 | N | $ 180,000 | $ 13,275 | 13.56 | ||||||||||||||||
|
|||||||||||||||||||||||
| 03 | view details |
RECOVER HEAT FROM ENGINE EXHAUSTS | 2.2433 | N | $ 8,000 | $ 1,443 | 5.54 | ||||||||||||||||
|
|||||||||||||||||||||||
| 04 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 432 | $ 1,293 | 0.33 | ||||||||||||||||
|
|||||||||||||||||||||||
| 05 | view details |
INSTALL OCCUPANCY SENSORS | 2.7135 | N | $ 3,600 | $ 1,245 | 2.89 | ||||||||||||||||
|
|||||||||||||||||||||||
| 06 | view details |
USE MOST EFFICIENT EQUIPMENT AT IT'S MAXIMUM CAPACITY AND LESS EFFICIENT EQUIPMENT ONLY WHEN NECESSARY | 2.6221 | I | $ 2,000 | $ 4,915 | 0.41 | ||||||||||||||||
|
|||||||||||||||||||||||
| 07 | view details |
ADD AREA LIGHTING SWITCHES | 2.7131 | N | $ 1,200 | $ 478 | 2.51 | ||||||||||||||||
|
|||||||||||||||||||||||
| 08 | view details |
REDUCE GLAZED AREAS IN BUILDINGS | 2.7421 | I | $ 1,400 | $ 5,285 | 0.26 | ||||||||||||||||
|
|||||||||||||||||||||||
| 09 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | N | $ 4,000 | $ 6,233 | 0.64 | ||||||||||||||||
|
|||||||||||||||||||||||
| 10 | view details |
INSTALL FOSSIL FUEL MAKE-UP AIR UNIT | 2.7235 | N | $ 2,115 | $ 10,722 | 0.20 | ||||||||||||||||
|
|||||||||||||||||||||||