Industrial Assessment Centers

Assessment #MZ0062


Assessment Year 2011
SIC 3499
SIC Description Fabricated Metal Products, Nec
NAICS 332999
NAICS Description All Other Miscellaneous Fabricated Metal Product Manufacturing
Principal Product Steel couplings for hydraulic hoses
Sales $ 50,000,000
# of Employees 100
Plant Area (Sq.Ft.) 80,000
Annual Production 60,000,000 Pieces
Production Hrs. Annual 8,000
Location (State) MO
Yearly Energy Cost $ 808,876

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

7,709,300 kWh $ 462,192 $ 0.060 /kWh

- Demand Charge

15,887 kW $ 127,096 $ 8.00 /kW

- Electricity Fees

- $ 0 -

Natural Gas

31,823 MMBtu $ 219,588 $ 6.90 /MMBtu

TOTAL ENERGY

110,844 MMBtu $ 808,876 $ 7.30 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

2,380,324 kWh
1,084,354 kWh
$ 140,519
$ 62,761
30.40 %
13.58 %
$ 0.060 /kWh

- Demand Charge

2,504 kW
632 kW
$ 20,040
$ 5,064
15.77 %
3.98 %
$ 8.00 /kW

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

10,530 MMBtu
7,569 MMBtu
$ 72,663
$ 52,233
33.09 %
23.79 %
$ 6.90 /MMBtu

TOTAL ENERGY

34,929 MMBtu
18,684 MMBtu
$ 233,221
$ 120,057
28.83 %
14.84 %
$ 7.30 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS 2.4221 I $ 1,160 $ 7,242 0.16
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

120,706 kWh $ 7,242 $ 0.060 /kWh

TOTAL ENERGY

1,237 MMBtu $ 7,242 -
02 view
details
USE MORE EFFICIENT LIGHT SOURCE 2.7143 I $ 49,280 $ 31,772 1.55
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

420,272 kWh $ 25,216 $ 0.060 /kWh

- Demand Charge

819 kW $ 6,556 $ 8.00 /kW

TOTAL ENERGY

4,308 MMBtu $ 31,772 -
03 view
details
INSTALL OCCUPANCY SENSORS 2.7135 N $ 1,840 $ 1,292 1.42
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

21,535 kWh $ 1,292 $ 0.060 /kWh

TOTAL ENERGY

221 MMBtu $ 1,292 -
04 view
details
INSTALL SPECTRAL REFLECTORS / DELAMP 2.7144 I $ 100 $ 1,360 0.07
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

18,880 kWh $ 1,133 $ 0.060 /kWh

- Demand Charge

28 kW $ 227 $ 8.00 /kW

TOTAL ENERGY

194 MMBtu $ 1,360 -
05 view
details
USE PROPER THICKNESS OF INSULATION ON BUILDING ENVELOPE 2.7492 N $ 1,498 $ 866 1.73
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

126 MMBtu $ 866 $ 6.90 /MMBtu

TOTAL ENERGY

126 MMBtu $ 866 -
06 view
details
USE WASTE HEAT TO PRODUCE STEAM TO DRIVE A STEAM TURBINE-GENERATOR 2.3412 N $ 250,000 $ 89,844 2.78
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

1,247,803 kWh $ 74,868 $ 0.060 /kWh

- Demand Charge

1,872 kW $ 14,976 $ 8.00 /kW

TOTAL ENERGY

12,790 MMBtu $ 89,844 -
07 view
details
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES 2.4236 I $ 1,300 $ 26,441 0.05
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

440,690 kWh $ 26,441 $ 0.060 /kWh

TOTAL ENERGY

4,517 MMBtu $ 26,441 -
08 view
details
ELIMINATE OR REDUCE COMPRESSED AIR USED FOR COOLING, AGITATING LIQUIDS, MOVING PRODUCT, OR DRYING 2.4232 I $ 15,000 $ 8,105 1.85
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

112,055 kWh $ 6,723 $ 0.060 /kWh

- Demand Charge

173 kW $ 1,382 $ 8.00 /kW

TOTAL ENERGY

1,149 MMBtu $ 8,105 -
09 view
details
ELIMINATE OR REDUCE COMPRESSED AIR USED FOR COOLING, AGITATING LIQUIDS, MOVING PRODUCT, OR DRYING 2.4232 I $ 9,000 $ 4,053 2.22
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

56,028 kWh $ 3,362 $ 0.060 /kWh

- Demand Charge

86 kW $ 691 $ 8.00 /kW

TOTAL ENERGY

574 MMBtu $ 4,053 -
10 view
details
USE FLUE GAS HEAT TO PREHEAT BOILER FEEDWATER 2.2412 N $ 30,000 $ 19,502 1.54
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

2,826 MMBtu $ 19,502 $ 6.90 /MMBtu

TOTAL ENERGY

2,826 MMBtu $ 19,502 -
11 view
details
USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT COMBUSTION AIR 2.2411 I $ 10,000 $ 17,836 0.56
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

2,584 MMBtu $ 17,836 $ 6.90 /MMBtu

TOTAL ENERGY

2,584 MMBtu $ 17,836 -
12 view
details
USE PROPER THICKNESS OF INSULATION ON BUILDING ENVELOPE 2.7492 N $ 60 $ 62 0.97
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

9 MMBtu $ 62 $ 6.90 /MMBtu

TOTAL ENERGY

9 MMBtu $ 62 -
13 view
details
USE SEPARATE SWITCHES ON PERIMETER LIGHTING WHICH MAY BE TURNED OFF WHEN NATURAL LIGHT IS AVAILABLE 2.7133 I $ 300 $ 91 3.30
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

1,512 kWh $ 91 $ 0.060 /kWh

TOTAL ENERGY

15 MMBtu $ 91 -
14 view
details
REPLACE FOSSIL FUEL EQUIPMENT WITH ELECTRICAL EQUIPMENT 2.1321 I $ 150,000 $ 11,657 12.87
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

-315,789 kWh $ -18,947 $ 0.060 /kWh

- Demand Charge

-474 kW $ -3,792 $ 8.00 /kW

Natural Gas

4,985 MMBtu $ 34,397 $ 6.90 /MMBtu

TOTAL ENERGY

1,748 MMBtu $ 11,657 -
15 view
details
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS 2.4141 N $ 1,500 $ 1,598 0.94
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

26,632 kWh $ 1,598 $ 0.060 /kWh

TOTAL ENERGY

273 MMBtu $ 1,598 -
16 view
details
UPGRADE CONTROLS ON COMPRESSORS 2.4224 I $ 18,000 $ 11,500 1.57
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

230,000 kWh $ 11,500 $ 0.060 /kWh

TOTAL ENERGY

2,358 MMBtu $ 11,500 -