Industrial Assessment Centers
Assessment #MA0446
| Assessment Year | 1999 |
|---|---|
| SIC | 3825 |
| SIC Description | Instruments To Measure Electricity |
| NAICS | |
| NAICS Description | |
| Principal Product | Dimensional Measurement Instrumentation |
| Sales | $ 50,000,000 |
| # of Employees | 380 |
| Plant Area (Sq.Ft.) | 143,300 |
| Annual Production | 0 Not Available |
| Production Hrs. Annual | 6,846 |
| Location (State) | RI |
| Yearly Energy Cost | $ 332,116 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
4,267,585 kWh | $ 253,587 | $ 0.059 /kWh |
- Demand Charge |
11,097 kW | $ 36,817 | $ 3.32 /kW |
- Electricity Fees |
- | $ 4,117 | - |
Natural Gas |
7,503 MMBtu | $ 37,595 | $ 5.01 /MMBtu |
TOTAL ENERGY |
51,246 MMBtu | $ 332,116 | $ 6.48 /MMBtu |
Water Disposal |
9,023,078 Gal | $ 18,806 | $ 0 /Gal |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
1,449,005 kWh 139,801 kWh |
$ 88,887 $ 8,705 |
35.05 % 3.43 % |
$ 0.059 /kWh |
- Demand Charge |
1,543 kW 144 kW |
$ 4,232 $ 382 |
11.49 % 1.04 % |
$ 3.32 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
-1,155 MMBtu 2,242 MMBtu |
$ -5,974 $ 11,589 |
-15.89 % 30.83 % |
$ 5.01 /MMBtu |
TOTAL ENERGY |
13,696 MMBtu 3,674 MMBtu |
$ 87,145 $ 20,676 |
26.24 % 6.23 % |
$ 6.48 /MMBtu |
Water Disposal |
3,942,000 Gal 3,942,000 Gal |
$ 7,648 $ 7,648 |
40.67 % 40.67 % |
$ 0 /Gal |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT | 2.1311 | N | $ 36,700 | $ 30,897 | 1.19 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 02 | view details |
INSULATE BARE EQUIPMENT | 2.2511 | N | $ 820 | $ 30,690 | 0.03 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 03 | view details |
REPLACE CITY WATER WITH RECYCLED WATER VIA COOLING TOWER | 3.4114 | I | $ 20,800 | $ 14,463 | 1.44 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 04 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | I | $ 3,575 | $ 9,237 | 0.39 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 05 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 12,279 | $ 3,234 | 3.80 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 06 | view details |
VENTILATION SYSTEM TO SHUT OFF WHEN ROOM IS NOT IN USE | 2.7311 | I | $ 0 | $ 2,849 | 0.00 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 07 | view details |
AIR CONDITION ONLY SPACE IN USE | 2.7222 | I | $ 2,670 | $ 1,137 | 2.35 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 08 | view details |
USE ADJUSTABLE FREQUENCY DRIVE TO REPLACE THROTTLING SYSTEM | 2.4143 | N | $ 4,225 | $ 930 | 4.54 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 09 | view details |
REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT | 2.1311 | N | $ 2,000 | $ 718 | 2.79 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||
| 10 | view details |
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS | 2.4221 | I | $ 300 | $ 638 | 0.47 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||