Industrial Assessment Centers

Assessment #LL0353


Assessment Year 2011
SIC 3731
SIC Description Ship Building And Repairing
NAICS 336611
NAICS Description Ship Building and Repairing
Principal Product Ships
Sales $ 100,000,000
# of Employees 518
Plant Area (Sq.Ft.) 384,000
Annual Production 4 Pieces
Production Hrs. Annual 5,200
Location (State) LA
Yearly Energy Cost $ 212,773

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

2,828,066 kWh $ 212,773 $ 0.075 /kWh

- Electricity Fees

- $ 0 -

TOTAL ENERGY

28,988 MMBtu $ 212,773 $ 7.34 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

1,533,385 kWh
964,323 kWh
$ 115,373
$ 72,556
54.22 %
34.10 %
$ 0.075 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

TOTAL ENERGY

15,717 MMBtu
9,884 MMBtu
$ 115,373
$ 72,556
54.22 %
34.10 %
$ 7.34 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES 2.4236 I $ 22,440 $ 72,556 0.31
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

964,323 kWh $ 72,556 $ 0.075 /kWh

TOTAL ENERGY

9,884 MMBtu $ 72,556 -
02 view
details
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED 2.4231 N $ 30 $ 23,693 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

314,900 kWh $ 23,693 $ 0.075 /kWh

TOTAL ENERGY

3,228 MMBtu $ 23,693 -
03 view
details
REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS 2.7224 N $ 990 $ 15,381 0.06
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

204,422 kWh $ 15,381 $ 0.075 /kWh

TOTAL ENERGY

2,095 MMBtu $ 15,381 -
04 view
details
BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE 4.611 N $ 1,200 $ 3,312 0.36
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

24,080 kWh $ 1,812 $ 0.075 /kWh

TOTAL ENERGY

247 MMBtu $ 1,812 -

One-time Revenue or Avoided Cost

- $ 1,500 -

TOTAL PRODUCTON

- $ 1,500 -
05 view
details
CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES 2.6211 N $ 1,470 $ 1,052 1.40
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

13,978 kWh $ 1,052 $ 0.075 /kWh

TOTAL ENERGY

143 MMBtu $ 1,052 -
06 view
details
INSTALL OCCUPANCY SENSORS 2.7135 N $ 2,275 $ 594 3.83
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

7,891 kWh $ 594 $ 0.075 /kWh

TOTAL ENERGY

81 MMBtu $ 594 -
07 view
details
CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES 2.6211 N $ 88 $ 270 0.33
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

3,591 kWh $ 270 $ 0.075 /kWh

TOTAL ENERGY

37 MMBtu $ 270 -
08 view
details
USE PHOTOCELL CONTROLS 2.7134 N $ 90 $ 15 5.98
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

200 kWh $ 15 $ 0.075 /kWh

TOTAL ENERGY

2 MMBtu $ 15 -