Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
1,132,912 kWh | $ 118,976 | $ 0.105 /kWh |
- Demand Charge |
3,302 kW | $ 93,825 | $ 28.41 /kW |
- Electricity Fees |
- | $ 17,172 | - |
Natural Gas |
50,699 MMBtu | $ 430,105 | $ 8.48 /MMBtu |
TOTAL ENERGY |
62,311 MMBtu | $ 660,078 | $ 10.59 /MMBtu |
Water Disposal |
707,933 Gal | $ 300,000 | $ 0 /Gal |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
291,716 kWh 128,236 kWh |
$ 30,599 $ 13,465 |
25.72 % 11.32 % |
$ 0.105 /kWh |
- Demand Charge |
901 kW 312 kW |
$ 25,610 $ 8,870 |
27.30 % 9.45 % |
$ 28.41 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
6,652 MMBtu 2,140 MMBtu |
$ 56,407 $ 18,148 |
13.11 % 4.22 % |
$ 8.48 /MMBtu |
TOTAL ENERGY |
9,642 MMBtu 3,454 MMBtu |
$ 112,616 $ 40,483 |
17.06 % 6.13 % |
$ 10.59 /MMBtu |
Water Disposal |
0 Gal 0 Gal |
$ 0 $ 0 |
0.00 % 0.00 % |
$ 0 /Gal |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS | 2.3131 | N | $ 3,000 | $ 4,689 | 0.64 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 02 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | N | $ 13,920 | $ 5,390 | 2.58 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 03 | view details |
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS | 2.7142 | I | $ 13,428 | $ 14,612 | 0.92 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 04 | view details |
INSTALL OCCUPANCY SENSORS | 2.7135 | N | $ 3,590 | $ 2,652 | 1.35 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 05 | view details |
REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL | 2.7232 | I | $ 9,800 | $ 7,198 | 1.36 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 06 | view details |
USE ADJUSTABLE FREQUENCY DRIVE TO REPLACE MOTOR-GENERATOR SET | 2.4142 | N | $ 70,000 | $ 21,354 | 3.28 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 07 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | I | $ 1,000 | $ 6,280 | 0.16 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 08 | view details |
PREHEAT COMBUSTION AIR WITH WASTE HEAT | 2.2442 | N | $ 20,000 | $ 11,007 | 1.82 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 09 | view details |
ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO | 2.1233 | N | $ 20,000 | $ 28,832 | 0.69 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 10 | view details |
REPAIR OR REPLACE STEAM TRAPS | 2.2113 | I | $ 0 | $ 13,433 | 0.00 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
| 11 | view details |
REPLACE EXISTING EQUIPMENT WITH MORE SUITABLE SUBSTITUTES | 4.652 | N | $ 10,500 | $ 59,246 | 0.18 | ||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||