Industrial Assessment Centers

Assessment #KU0148


Assessment Year 1984
SIC 3699
SIC Description Electrical Equipment & Supplies, Nec
NAICS
NAICS Description
Principal Product AVIATION ELECTRONICS
Sales $ 35,000,000
# of Employees 350
Plant Area (Sq.Ft.) 0
Annual Production 25,000 Pieces
Production Hrs. Annual 6,000
Location (State) KS
Yearly Energy Cost $ 103,595

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

1,315,944 kWh $ 94,060 $ 0.071 /kWh

- Electricity Fees

- $ 0 -

Natural Gas

2,034 MMBtu $ 9,535 $ 4.69 /MMBtu

TOTAL ENERGY

15,522 MMBtu $ 103,595 $ 6.67 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

294,256 kWh
88,805 kWh
$ 23,783
$ 9,094
25.28 %
9.67 %
$ 0.071 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

1,890 MMBtu
1,986 MMBtu
$ 8,862
$ 9,315
92.94 %
97.69 %
$ 4.69 /MMBtu

TOTAL ENERGY

4,905 MMBtu
2,896 MMBtu
$ 32,645
$ 18,409
31.51 %
17.77 %
$ 6.67 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 I $ 36 $ 4,910 0.01
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

68,875 kWh $ 4,910 $ 0.071 /kWh

TOTAL ENERGY

706 MMBtu $ 4,910 -
02 view
details
USE DEMAND CONTROLLER OR LOAD SHEDDER 2.3191 I $ 3,000 $ 2,754 1.09
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

0 kWh $ 2,754 $ 0.071 /kWh

TOTAL ENERGY

0 MMBtu $ 2,754 -
03 view
details
ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO 2.1233 I $ 800 $ 514 1.56
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

122 MMBtu $ 572 $ 4.69 /MMBtu

TOTAL ENERGY

122 MMBtu $ 572 -

Administrative Changes

- $ -58 -

TOTAL PRODUCTON

- $ -58 -
04 view
details
INSTALL AUTOMATIC STACK DAMPER 2.1123 I $ 700 $ 436 1.61
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

93 MMBtu $ 436 $ 4.69 /MMBtu

TOTAL ENERGY

93 MMBtu $ 436 -
05 view
details
REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC 2.1131 I $ 100 $ 366 0.27
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

78 MMBtu $ 366 $ 4.69 /MMBtu

TOTAL ENERGY

78 MMBtu $ 366 -
06 view
details
INSULATE BARE EQUIPMENT 2.2511 N $ 70 $ 173 0.40
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

2,638 kWh $ 199 $ 0.071 /kWh

Natural Gas

-5 MMBtu $ -26 $ 4.69 /MMBtu

TOTAL ENERGY

22 MMBtu $ 173 -
07 view
details
INSULATE BARE EQUIPMENT 2.2511 N $ 1,240 $ 1,738 0.71
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

24,326 kWh $ 1,738 $ 0.071 /kWh

TOTAL ENERGY

249 MMBtu $ 1,738 -
08 view
details
RECOVER WASTE HEAT FROM EQUIPMENT 2.2437 N $ 150 $ 99 1.52
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

34 MMBtu $ 159 $ 4.69 /MMBtu

TOTAL ENERGY

34 MMBtu $ 159 -

Administrative Changes

- $ -60 -

TOTAL PRODUCTON

- $ -60 -
09 view
details
REPLACE BROKEN WINDOWS AND/OR WINDOW SASH 2.7441 I $ 12 $ 298 0.04
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

293 kWh $ 21 $ 0.071 /kWh

Natural Gas

59 MMBtu $ 277 $ 4.69 /MMBtu

TOTAL ENERGY

62 MMBtu $ 298 -
10 view
details
REDUCE VENTILATION AIR 2.7314 I $ 500 $ 2,954 0.17
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

-15,240 kWh $ -1,089 $ 0.071 /kWh

Natural Gas

862 MMBtu $ 4,043 $ 4.69 /MMBtu

TOTAL ENERGY

706 MMBtu $ 2,954 -
11 view
details
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS 2.4141 N $ 15,000 $ 10,658 1.41
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

149,179 kWh $ 10,658 $ 0.071 /kWh

TOTAL ENERGY

1,529 MMBtu $ 10,658 -
12 view
details
LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA 2.7221 I $ 17 $ 4,177 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

24,326 kWh $ 1,738 $ 0.071 /kWh

Natural Gas

520 MMBtu $ 2,439 $ 4.69 /MMBtu

TOTAL ENERGY

769 MMBtu $ 4,177 -
13 view
details
IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS 2.7243 I $ 2,000 $ 1,182 1.69
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

252 MMBtu $ 1,182 $ 4.69 /MMBtu

TOTAL ENERGY

252 MMBtu $ 1,182 -
14 view
details
REDUCE HOT WATER TEMPERATURE TO THE MINIMUM REQUIRED 2.6121 I $ 0 $ 760 0.00
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

10,551 kWh $ 760 $ 0.071 /kWh

TOTAL ENERGY

108 MMBtu $ 760 -
15 view
details
REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT 2.1311 N $ 1,900 $ 1,508 1.26
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

29,308 kWh $ 2,094 $ 0.071 /kWh

Natural Gas

-125 MMBtu $ -586 $ 4.69 /MMBtu

TOTAL ENERGY

175 MMBtu $ 1,508 -