Industrial Assessment Centers
Assessment #DL0055
| Assessment Year | 2010 |
|---|---|
| SIC | 2086 |
| SIC Description | Bottled And Canned Soft Drinks |
| NAICS | 312111 |
| NAICS Description | Soft Drink Manufacturing |
| Principal Product | Carbonated/Non-carbonated Beverage |
| Sales | $ 92,500,000 |
| # of Employees | 150 |
| Plant Area (Sq.Ft.) | 125,000 |
| Annual Production | 30,000,000 Pieces |
| Production Hrs. Annual | 7,054 |
| Location (State) | PA |
| Yearly Energy Cost | $ 771,500 |
Current Energy Usage & Costs
| Energy Sources | Yearly Usage | Yearly Cost | Unit Price |
|---|---|---|---|
Electricity |
7,472,000 kWh | $ 465,000 | $ 0.062 /kWh |
- Demand Charge |
1,446 kW | $ 20,600 | $ 14.25 /kW |
- Electricity Fees |
- | $ 0 | - |
Natural Gas |
45,916 MMBtu | $ 285,900 | $ 6.23 /MMBtu |
TOTAL ENERGY |
122,504 MMBtu | $ 771,500 | $ 6.30 /MMBtu |
Recommended Reduction in Usage & Costs
|
Recommended Implemented |
| Energy Sources | Yearly Savings | Yearly Cost | % Saved | Unit Price |
|---|---|---|---|---|
Electricity |
1,821,632 kWh 1,028,342 kWh |
$ 119,339 $ 76,307 |
25.66 % 16.41 % |
$ 0.062 /kWh |
- Demand Charge |
2,999 kW 1,650 kW |
$ 29,621 $ 23,568 |
143.79 % 114.41 % |
$ 14.25 /kW |
- Electricity Fees |
- |
$ 0 $ 0 |
0.00 % 0.00 % |
- |
Natural Gas |
26,276 MMBtu 2,290 MMBtu |
$ 186,832 $ 16,262 |
65.35 % 5.69 % |
$ 6.23 /MMBtu |
TOTAL ENERGY |
44,948 MMBtu 12,830 MMBtu |
$ 335,792 $ 116,137 |
43.52 % 15.05 % |
$ 6.30 /MMBtu |
Recommendations
| AR # | Description | ARC Code | Status | Cost | Savings | Payback (Years) |
|||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | view details |
RECOVER HEAT FROM REFRIGERATION CONDENSERS | 2.2436 | N | $ 13,000 | $ 31,870 | 0.41 | ||||||||||||||||
|
|||||||||||||||||||||||
| 02 | view details |
REPLACE BOILER | 2.1224 | N | $ 102,000 | $ 59,500 | 1.71 | ||||||||||||||||
|
|||||||||||||||||||||||
| 03 | view details |
OPERATE BOILERS ON HIGH FIRE SETTING | 2.1212 | N | $ 50 | $ 35,000 | 0.00 | ||||||||||||||||
|
|||||||||||||||||||||||
| 04 | view details |
REPLACE TREATED WATER WITH WELL / SURFACE WATER | 3.4159 | N | $ 100,000 | $ 39,150 | 2.55 | ||||||||||||||||
|
|||||||||||||||||||||||
| 05 | view details |
USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS | 2.4141 | I | $ 125,000 | $ 82,808 | 1.51 | ||||||||||||||||
|
|||||||||||||||||||||||
| 06 | view details |
USE DIRECT AIR SUPPLY TO EXHAUST HOODS | 2.7245 | I | $ 3,000 | $ 9,000 | 0.33 | ||||||||||||||||
|
|||||||||||||||||||||||
| 07 | view details |
ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES | 2.4236 | I | $ 1,200 | $ 12,600 | 0.10 | ||||||||||||||||
|
|||||||||||||||||||||||
| 08 | view details |
REDUCE VENTILATION AIR | 2.7314 | N | $ 15,000 | $ 21,000 | 0.71 | ||||||||||||||||
|
|||||||||||||||||||||||
| 09 | view details |
RECYCLE AIR FOR HEATING, VENTILATION AND AIR CONDITIONING | 2.7313 | N | $ 15,000 | $ 23,200 | 0.65 | ||||||||||||||||
|
|||||||||||||||||||||||
| 10 | view details |
KEEP EQUIPMENT CLEAN | 2.6125 | I | $ 500 | $ 3,631 | 0.14 | ||||||||||||||||
|
|||||||||||||||||||||||
| 11 | view details |
USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT | 2.7233 | I | $ 1,830 | $ 3,631 | 0.50 | ||||||||||||||||
|
|||||||||||||||||||||||
| 12 | view details |
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED | 2.4231 | I | $ 6,000 | $ 4,467 | 1.34 | ||||||||||||||||
|
|||||||||||||||||||||||
| 13 | view details |
UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS | 2.4111 | N | $ 2,840 | $ 9,935 | 0.29 | ||||||||||||||||
|
|||||||||||||||||||||||