Industrial Assessment Centers

Assessment #BD0345


Assessment Year 2008
SIC 2499
SIC Description Wood Products, Nec
NAICS 321999
NAICS Description All Other Miscellaneous Wood Product Manufacturing
Principal Product Sketchboards,Arthorse,Linoblocks,Pallets
Sales $ 264,811
# of Employees 13
Plant Area (Sq.Ft.) 24,000
Annual Production 61,712 Pounds
Production Hrs. Annual 2,340
Location (State) IL
Yearly Energy Cost $ 40,406

Current Energy Usage & Costs

Energy Sources Yearly Usage Yearly Cost Unit Price

Electricity

270,264 kWh $ 27,623 $ 0.102 /kWh

- Electricity Fees

- $ 0 -

Natural Gas

1,267 MMBtu $ 12,783 $ 10.09 /MMBtu

TOTAL ENERGY

4,037 MMBtu $ 40,406 $ 10.01 /MMBtu

Recommended Reduction in Usage & Costs

Recommended
Implemented
Energy Sources Yearly Savings Yearly Cost % Saved Unit Price

Electricity

200 kWh
184 kWh
$ 5,185
$ 4,772
18.77 %
17.28 %
$ 0.102 /kWh

- Electricity Fees

- $ 0
$ 0
0.00 %
0.00 %
-

Natural Gas

340 MMBtu
340 MMBtu
$ 3,422
$ 3,422
26.77 %
26.77 %
$ 10.09 /MMBtu

TOTAL ENERGY

342 MMBtu
342 MMBtu
$ 8,607
$ 8,194
21.30 %
20.28 %
$ 10.01 /MMBtu

Recommendations

AR # Description ARC Code Status Cost Savings Payback
(Years)
01 view
details
USE MORE EFFICIENT LIGHT SOURCE 2.7143 I $ 6,840 $ 2,896 2.36
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

111 kWh $ 2,896 $ 0.102 /kWh

TOTAL ENERGY

1 MMBtu $ 2,896 -
02 view
details
INSTALL OCCUPANCY SENSORS 2.7135 N $ 725 $ 413 1.76
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

16 kWh $ 413 $ 0.102 /kWh

TOTAL ENERGY

0 MMBtu $ 413 -
03 view
details
UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS 2.7142 I $ 550 $ 324 1.70
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

5 kWh $ 131 $ 0.102 /kWh

TOTAL ENERGY

0 MMBtu $ 131 -

Personnel Changes

- $ 81 -

Administrative Changes

- $ 112 -

TOTAL PRODUCTON

- $ 193 -
04 view
details
INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS 2.4221 I $ 300 $ 330 0.91
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

13 kWh $ 330 $ 0.102 /kWh

TOTAL ENERGY

0 MMBtu $ 330 -
05 view
details
REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED 2.4231 I $ 1,000 $ 1,343 0.74
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

52 kWh $ 1,343 $ 0.102 /kWh

TOTAL ENERGY

1 MMBtu $ 1,343 -
06 view
details
USE RADIANT HEATER FOR SPOT HEATING 2.7231 I $ 10,592 $ 3,422 3.10
Energy Sources Yearly Reduction Yearly Savings Unit Price

Natural Gas

340 MMBtu $ 3,422 $ 10.09 /MMBtu

TOTAL ENERGY

340 MMBtu $ 3,422 -
07 view
details
USE SYNTHETIC LUBRICANT 2.4314 I $ 100 $ 72 1.39
Energy Sources Yearly Reduction Yearly Savings Unit Price

Electricity

3 kWh $ 72 $ 0.102 /kWh

TOTAL ENERGY

0 MMBtu $ 72 -